UEEEL0005 Coverage with Control Circuit and Motor Starter Pracboxes
At a glance
Using the Control Circuit Pracbox and Motor Starter Pracbox together, you can support delivery and assessment of UEEEL0005 with strong practical coverage:
- Performance Criteria: 100%
- Performance Evidence: 99%
- Knowledge Evidence: 86%
Key remaining performance gap: torque measurement
We can also supply a torque sensor if required.
Introduction
In the VET sector, delivery and assessment need to align with the requirements of the unit being taught. ASQA expects RTOs and TAFEs to ensure their assessment is valid, which means it should align with the unit of competency and cover the skills and knowledge required for competent performance. The 2025 Standards for RTOs also require assessment systems to be quality assured through validation of assessment practices and judgements.
While formal validation usually focuses on assessment tools and outcomes, we also map our equipment against unit requirements so customers can clearly see how it supports delivery and assessment of UEEEL0005.
Mapping the Control Circuit and Motor Starter Pracboxes to UEEEL0005
The Control Circuit Pracbox was already able to cover a large portion of UEEEL0005, but not the full practical scope of the unit on its own.
The Motor Starter Pracbox was developed to help address those remaining gaps.
Together, the two Pracboxes provide near-complete coverage of the practical requirements of UEEEL0005, while also supporting a large portion of the knowledge evidence.
This gives trainers a clearer pathway for delivery and assessment, and helps training organisations get a stronger return on investment from the equipment.
Mapping of Elements and Performance Criteria
The Elements and Performance Criteria of UEEEL0005 are divided into three sections. Together, the Control Circuit Pracbox and Motor Starter Pracbox cover 100% of these requirements.
The table below shows how the two Pracboxes map to the Elements and Performance Criteria of UEEEL0005. Click the plus icon to expand each section and view the detailed coverage.
| Elements & Performance Criteria | ||
| EPC1 | Develop electrical control circuits | 100% |
| EPC1.1 | WHS/OHS requirements and workplace procedures for a given work area are identified obtained and applied | Y |
| EPC1.2 | Control circuit/s requirements are determined from discussions with relevant person/s and documented in accordance with workplace procedures | Y |
| EPC1.3 | Agreement for the control circuit/s requirement is sought from appropriate person/s and documented in accordance with workplace procedures | Y |
| EPC1.4 | Schematic arrangement of control circuits that complies with agreed requirement is documented in accordance with workplace procedures | Y |
| EPC1.5 | Wiring diagram of control circuits is developed from schematic diagram in accordance with workplace procedures | Y |
| EPC1.6 | Materials needed to connect control circuit/s are obtained in accordance with workplace procedures and checked against job requirements | Y |
| EPC1.7 | Tools, equipment and testing devices needed to connect control circuit/s are obtained in accordance with workplace procedures and checked for correct operation and safety | Y |
| EPC1.8 | Preparatory work is checked to ensure no damage has occurred and complies with control circuit/s application requirements | Y |
| EPC2 | Connect and test electrical control circuits | 100% |
| EPC2.1 | WHS/OHS risk control measures and workplace procedures for carrying out work are followed | Y |
| EPC2.2 | Need to test or measure live electrical work is determined in accordance with WHS/OHS requirements and conducted within established safety workplace procedures | Y |
| EPC2.3 | Circuits/machines/plant are checked and isolated as required in accordance with WHS/OHS requirements and workplace procedures | Y |
| EPC2.4 | Control circuit component/s are connected to comply with the agreed control requirements | Y |
| EPC2.5 | Control circuit operation is tested for functionality and in accordance with WHS/OHS requirements and workplace safety procedures | Y |
| EPC2.6 | Non-compliant control functions are rectified | Y |
| EPC2.7 | Unplanned situations are dealt with safely and with the approval of an authorised person in accordance with workplace procedures in a manner that minimises risk to personnel and equipment | Y |
| EPC2.8 | Control circuits are connected, inspected and tested without unnecessary waste of materials or damage to apparatus, circuits, the surrounding environment or services using sustainable energy practice | Y |
| EPC3 | Complete and document circuit development activities | 100% |
| EPC3.1 | WHS/OHS work completion risk control measures and workplace procedures are followed | Y |
| EPC3.2 | Worksite is cleaned and made safe in accordance with workplace procedures | Y |
| EPC3.3 | ‘As-connected’ control circuits are documented using standard drawing conventions and appropriate person/s notified in accordance with workplace procedures | Y |
Mapping of Performance Evidence
The Performance Evidence of UEEEL0005 is divided into nine sections. Together, the Control Circuit Pracbox and Motor Starter Pracbox cover 99% of these requirements.
The remaining gap is torque measurement, which sits outside the two Pracboxes and requires an external torque sensor. We can also supply a torque sensor to support 100% coverage of this area.
The table below shows how the two Pracboxes map to the Performance Evidence of UEEEL0005. Click the plus icon to expand each section and view the detailed coverage.
| Performance Evidence | 99% | |
| PE1 | applying relevant work health and safety (WHS)/occupational health and safety (OHS) requirements and workplace procedures and practices, including using risk control measures | Y |
| PE2 | applying sustainable energy principles and practices | Y |
| PE3 | using manufacturers’ catalogues to select: | 100% |
| PE3.1 | circuit components for appropriate duty ratings | Y |
| PE3.2 | control devices for specified requirements | Y |
| PE3.3 | pushbuttons/pilot lamps for specific requirements | Y |
| PE3.4 | relays for specified requirements | Y |
| PE3.5 | the most suitable motor starter for a given situation | Y |
| PE3.6 | timers for specified functions | Y |
| PE4 | labelling wires and terminals | Y |
| PE5 | converting circuit (schematic) diagrams to wiring diagrams | Y |
| PE6 | developing: | 100% |
| PE6.1 | electrical control circuit in accordance with a written description (specification) and listing the sequence of operation of the circuit | Y |
| PE6.2 | forward reverse circuit requiring interlocking from a description of the circuit operation, including jog and interlock functions | Y |
| PE6.3 | control circuit incorporating local and remote start and stop buttons and electrical interlocking | Y |
| PE6.4 | simple stop-start control circuit that incorporates pilot lights and latching circuit | Y |
| PE6.5 | timer controlled circuits from a written description and listing the sequence of circuit operation | Y |
| PE7 | measuring starting current and torque of selected motor starters | 50% |
| PE8 | connecting and testing: | 100% |
| PE8.1 | circuit with a braking feature to operate a three phase motor | Y |
| PE8.2 | control devices into control circuits | Y |
| PE8.3 | direct-on-line (DOL) motor starter and testing the operation of the power and control circuits | Y |
| PE8.4 | variable speed drive (VSD) | Y |
| PE8.5 | electronic (soft) starter | Y |
| PE8.6 | electrical circuits with local and remote start-stop control | Y |
| PE8.7 | input and output devices to a programmable relay using a diagram | Y |
| PE8.8 | motor starter power and control circuits for correct operation | Y |
| PE8.9 | multiple motor starting circuit which incorporates start, stop and jog control | Y |
| PE8.10 | simple electrical control circuit from circuit diagrams | Y |
| PE8.11 | timer controlled circuit using a circuit diagram as a guide | Y |
| PE9 | completing and documenting circuit development activities. | Y |
Mapping of Knowledge Evidence
The Knowledge Evidence of UEEEL0005 is divided into 13 sections. Together, the Control Circuit Pracbox and Motor Starter Pracbox cover 86% of these requirements.
In many cases, Knowledge Evidence is assessed through theory-based assessment tools. We have included it in this mapping because we believe practical equipment should also support the assessment of knowledge wherever possible.
This gives training organisations a more holistic view of the candidate’s competence by showing not only whether they understand the theory, but also whether they can apply it in practice.
The table below shows how the two Pracboxes map to the Knowledge Evidence of UEEEL0005. Click the plus icon to expand each section and view the detailed coverage.
| Knowledge Evidence | 86% | |
| KE1 | operating principles, basic contact configurations and identification and common applications of: | 100% |
| KE1.1 | control relays | Y |
| KE1.2 | timers | Y |
| KE1.3 | contactors | Y |
| KE1.4 | thermal overloads | Y |
| KE2 | control circuits, including: | 75% |
| KE2.1 | converting circuit (schematic) diagrams to wiring diagrams | Y |
| KE2.2 | identification of circuit diagrams (schematic) symbols and explain the operation of components represented | Y |
| KE2.3 | switching configurations and common applications of push buttons | Y |
| KE2.4 | control circuit drawing conventions | K |
| KE3 | remote stop-start control and electrical interlocking, including: | 100% |
| KE3.1 | operation of: | |
| KE3.1.1 | local and remote start-stop control of relays | Y |
| KE3.1.2 | operation of an electrically interlocked control circuit | Y |
| KE3.2 | applying circuit checking and testing techniques to an electrical control circuit | Y |
| KE4 | time delay relays, including timer circuit checking and testing procedures | 100% |
| KE5 | circuits using contactors, including: | 100% |
| KE5.1 | circuit diagram symbols | Y |
| KE5.2 | circuit development using a contactor | Y |
| KE5.3 | using contactors for motor control | Y |
| KE6 | jogging and interlocking, including: | 100% |
| KE6.1 | purpose and application of: | |
| KE6.1.1 | jogging control of motors | Y |
| KE6.1.2 | electrical/mechanical interlocking | Y |
| KE6.2 | operation of motor control using start, stop and jog buttons | Y |
| KE7 | control devices, including: | 88% |
| KE7.1 | common control devices used in automatic control circuits: limit switches, proximity switches, photoelectric cells, pressure switches, float switches, light sensors and temperature sensors | P |
| KE7.2 | basic operating principles of common control devices | Y |
| KE7.3 | advantages and disadvantages of common control devices | Y |
| KE7.4 | applications for common control devices | Y |
| KE8 | programmable relays, including: | 100% |
| KE8.1 | advantages of programmable relays over electromagnetic control circuit control | Y |
| KE8.2 | typical applications of programmable relays | Y |
| KE8.3 | block diagram representation and basic operating principles | Y |
| KE8.4 | input and output parameters, listing, connections and output types | Y |
| KE8.5 | basic programming of ladder circuits consisting of inputs, outputs i.e. stop-start circuit | Y |
| KE8.6 | using the monitoring facility of the programmable relay to verify each ladder circuit operation | Y |
| KE8.7 | programming timers and using the monitoring facility of the programmable relay to check the values of the timer | Y |
| KE8.8 | external devices | Y |
| KE8.9 | implications of programming normally closed field devices | Y |
| KE8.10 | conversion of control circuits | Y |
| KE8.11 | common faults and their symptoms | Y |
| KE9 | three phase induction motor starters, including: | 67% |
| KE9.1 | reasons for limiting the starting current of large motors | K |
| KE9.2 | requirements of AS/NZS 3000 and the local supply authority requirements, with regard to starting and control of motors | K |
| KE9.3 | operating principles, applications and circuits for: | |
| KE9.3.1 | direct on line (DOL) starter | Y |
| KE9.3.2 | variable speed drive (VSD) | K |
| KE9.3.3 | variable frequency drive (VFD) | Y |
| KE9.3.4 | electronic (soft) starter | Y |
| KE10 | three phase induction motor starters- reduced voltage, including: | 33% |
| KE10.1 | operating principles and circuits for reduced voltage starters | K |
| KE10.2 | common applications for starter types | P |
| KE10.3 | comparison of motor starters basic characteristics | P |
| KE11 | three phase induction motor reversal and braking, including: | 50% |
| KE11.1 | operating principles and control circuits for reversal and braking methods | Y |
| KE11.2 | comparison of the different braking methods used | P |
| KE11.3 | typical applications for braking methods | K |
| KE12 | three phase induction motor speed control, including: | 100% |
| KE12.1 | operating principles and circuits for motor speed control | Y |
| KE13 | relevant manufacturer specifications | 100% |
Range of Conditions Coverage
The Range of Conditions for UEEEL0005 sets minimum requirements for the types of control circuits, devices, and sensors that must be included when developing, connecting, and functionally testing motor control circuits.
Using the Control Circuit Pracbox and Motor Starter Pracbox together, these requirements can be supported across all three areas listed below.
Summary
| Range of conditions area | Unit requirement | Coverage with the two Pracboxes |
| Electrical control circuits | At least 4 | 6 covered |
| Components and electrical devices | At least 3 | 6 covered |
| Transducers / sensors | At least 2 | 3 covered |
Electrical control circuits covered
- machine interlocked circuit
- machine safety circuit
- motor jogging circuit
- multiple stop-start circuit
- single stop-start circuit
- time controlled circuit
Components and electrical devices covered
- contactors
- programmable relays
- push buttons
- soft starters
- three phase starters
- variable speed drives
Transducers / sensors covered
- limit switches
- proximity switches
- timers
This allows training organisations to meet the minimum Range of Conditions requirements while using a practical and integrated training setup.